Pipe insulation

From Wikipedia, the free encyclopedia

Pipe Insulation is thermal insulation used to prevent heat loss and gain from pipes, to save energy and improve effectiveness of thermal systems.

The benefits include, in addition to reducing costs and environmental impacts of energy consumption:

  • Reducing or eliminating condensation on cold pipes.
  • Protection from dangerous pipe temperatures.
  • In domestic hot-water systems, the water temperature at the point of use can be closer to the temperature at the water heater, and wait time for hot water can be reduced
  • Control of noise.
  • Reduction of unwanted heat gain to air-conditioned spaces.

Heat flow calculations and R-value

The heat flow through pipe insulation with outer diameter do and inner diameter (of the insulation--equal to outer diameter of the pipe) di is

 Q=frac{ ell 2 pi k Delta T}{ ln(d_o / d_i)}

where ell is the length of the pipe, k is the thermal conductivity of the insulation material, and ΔT is the temperature difference between the inner and outer walls of the insulation. If the insulation is sufficiently thick and has sufficiently low thermal conductivity, the outside surface of the insulation will be close to the ambient temperature, and ΔT may be approximated as the temperature difference between the temperature of the fluid in the pipe and the ambient temperature.

thermal resistance R_{th}=frac{1}{ ell 2 pi k} ln(frac{d_o}{ d_i}).

For building envelope insulation in rectangular forms, R-value Rv is the thermal resistance of a unit-area (1 square foot or 1 square meter) section of insulation, such that

 R_v = R_{th} cdot A

where A is the surface area over which the thermal resistance is calculated. Applying this to pipe insulation is not straightforward, however, because the surface area used could be either the area of the inner cylinder

 A_i = ell pi d_i

or the area of the outer cylinder

 A_o = ell pi d_o.

The resulting R-values would be

 R_{v,i}=frac{d_i}{2 k} ln(frac{d_o}{ d_i})

or

 R_{v,o}=frac{d_o}{2 k} ln(frac{d_o}{ d_i})

R-values of pipe insulation are not covered by the US FTC R-value. R-values quoted by manufacturers normalize the thermal resistance to the outer diameter of the insulation  i.e., they provide

 R_{v,o}=frac{d_o}{2 k} ln(frac{d_o}{ d_i}).

This allows them to quote a higher number, but it is less useful for comparing different insulations because, for a given pipe that needs insulation, Ai is constant independent of the insulation chosen, whereas Ao depends on the insulation chosen.

From the manufacturer's quoted R-value Rv,o, on can calculate thermal resistance

 R_{th}=R_{v,o}/A = frac{R_{v,o}}{pi d_o ell}

and heat flow

 Q = Delta T/R_{th}=frac{Delta T pi d_o ell}{R_{v,o}}

Note that doing any of these calculations in imperial units (BTU, feet, hours, inches and fahrenheit) is hazardous because there is often a mix of inches and feet used, even within the units for one variable (such as k).

Shopping Cart more
0 items
Currencies
We accept...
PayPal
I accept Pound Sterling payments through PayPal!
Secure Website
Secure site protected by SSL
Secure Website
Card Watch web 
site logo
Bestsellers
01.28mm Pipe Insulation x 2m Slit Tubolit TL-28/13-DG 13mm Wall
02.42mm Pipe Insulation x 2m Slit Tubolit TL-42/13-DG 13mm Wall
03.48mm Pipe Insulation x 2m Slit Tubolit TL-48/13-DG 13mm Wall
04.60mm Pipe Insulation x 2m Slit Tubolit TL-60/13-DG 13mm Wall
05.35mm Pipe Insulation x 2m Slit Tubolit TL-35/13-DG 13mm Wall
06.54mm Pipe Insulation x 2m Slit Tubolit TL-54/13-DG 13mm Wall
07.Scaffold Protective Foam Pipe Tube Padding 2m x 49mm x 14mm
08.Green Protective Foam Scaffold Pole Post Padding 2.08m x 43mm x 15mm thick
09.Ice Blue Protective Foam Post Pole Padding 2.4m x 18mm thick 51mm Bore
10.Black Protective Foam Post Pole Padding 2.4m x 18mm thick 51mm Bore
What's New? more


£0.00 Exc
£0.00 Inc
Reviews more
There are currently no product reviews

 
Copyright © 2006 FoamPaddingDirect.co.uk
eShop Setup & Hosted by Kynet Ltd